- as per requirement
- Piece/Pieces
Changeover & By Pass Switch
Salient Features
- Modular design in 3 & 4 pole (63A ~3150A), suitable for utilization category AC-23A
- Easy maintenance as each pole can be replaced easily due to modular construction, saving cost of entire Switch in case of single pole being burnt or damaged.
- Available in open execution & in sheet steel enclosure.
- Complies with the latest requirements of IEC-60947-1 &3 13947-1 &3 standards.
- Unique self cleaning contact construction with special knife type (200A~1800A), double break switching contacts (63~160A & 1000~1800A) & single break (200A~800A). Positive opening operation, with quick make - break and effective arc splitting plates guarantee reliability and long electrical life of the Switch.
- Excellent tracking resistance of isolation material in switch frame prevents flashover between phases even in the most trying & difficult locations.
- Adjustable telescopic shaft
- Compact construction
- Window for visual contact inspection
- Suitable for capacitor switching and as a Main switch
- Handle with in-built padlockable facility in-off position
- Provision for defeating door interlock
- Individual phase barrier can be incorporated without tools, between two terminals. Fully protected frame for safe operation in case of (200A~800A)
Function:
- These changeover switches are used to control disconnect any kind of circuit-disconnection feeders both resistive & inductive loads
- By means of manual operation, changeover performs circuit switching between two independent circuits -I & ll
Accessories
- Auxiliary contact (early break type) 1NO + 1NC or 2NO+2NC is available
- Key & Castle lock facility
Technical Parameters:
Common Characteristics |
|
|
Conformity to Standards | - | IEC 60947-3 / IS 13947-3 |
No. of Poles | - | 3P / 4P |
Rated Operational Voltage (Ue) | V | 415 |
Rated Operational Frequency | Hz | 50 / 60 |
Suitability for Isolation | - | YES |
Pollution Degree as per IEC / IS | - | 3 |
Ambient / Cubicle Service Temperature | oC | 45 |
IP Level after mounting | - | IP 54 |
Technical Parameters compact on load changeover switch / compact On-load by pass switch
Replace '' with 3 in case of 3 pole or with 4 in case of 4 pole
Parameters |
| 63A | 80A | 100A |
Conventional Changeover Type CSSD |
| CSSD 63DCO | - | - |
On-Load Compact Bypass Switch Type CSBS |
| CSBS 63DM | CSBS 80DM | CSBS 100DM |
On-Load Compact Changeover Switch Type CSCS with shroting links |
| CSCS 63DMCO | CSCS 80DMCO | CSCS 100DMCO |
On-Load Compact Changeover Switch Type CSCS without shorting links |
| - | - | - |
Current rating at 45o C | Ith (A) | 63 | 80 | 100 |
No. of Pole |
| 3/4 | 3/4 | 3/4 |
Rated insulation Voltage Ui | V | 1000 | 1000 | 1000 |
Maximum operational voltage Ue max | V | 690 | 690 | 690 |
Di-electric strength at 50Hz for 1 min. | KV | 3.5 | 3.5 | 3.5 |
Rated impulse voltage Uimp | KV | 12 | 12 | 12 |
Rated operational current le at 415 V |
|
|
|
|
Rated making capacity at 415V, 0.35 pf |
|
|
|
|
Rated breaking capacity at 415V, 0.35 pf |
|
|
|
|
Capacitor rating at 415V, 3ph | kVAR | 50 | 50 | 50 |
Short circuit current with fuses | KA r.m.s | 50 | 50 | 50 |
Rated short circuit making capacity (peak) | kA | 10 | 10 | 10 |
Short time current for 1 sec. | kA.r.m.s | 5 | 5 | 5 |
Electrical Endurance | Operations | 5000 | 5000 | 5000 |
#Mechanical Endurance | Operations | 10000 | 10000 | 10000 |
#Mechanical Endurance also includes Electrical Endurance
- Cash on Delivery (COD), Cash Advance (CA), Cash in Advance (CID), Cheque, Days after Acceptance (DA), Delivery Point (DP), Letter of Credit (L/C), Letter of Credit at Sight (Sight L/C), Telegraphic Transfer (T/T), Western Union, Paypal
- 1 Days
- All India
A-7, Opp. Vaishali Nagar Police Station, Vaishali Nagar, Jaipur, Rajasthan, 302021, India
Phone :+918045479989